CRITICAL LOAD OUTPUT

Output Voltage:

Standard voltages—208Y/120 VAC, 480Y/277 VAC, 600Y/346 VAC. Other

 

voltages available on request.

 

SCC output: 3-phase, 3-wire plus ground or 3-phase, 4-wire plus ground.

 

Module output to SCC: 3-phase, 4-wire plus ground (neutral required).

 

Optional voltages—208 VAC, 480 VAC, 600 VAC. Other optional voltages

 

available on request. 3-phase, 3-wire plus ground (ungrounded or corner

 

grounded delta).

Voltage Regulation:

±0.5% for balanced load.

 

±2% for unbalanced load.

Voltage Adjustment Range:

±5% manually.

 

 

Line Drop Compensation Range:

Up to +5% automatic load dependent.

 

 

Frequency

59.5 Hz to 60.5 Hz.

 

 

Slew Rate:

0.06 Hz per second.

 

 

Phase Balancing:

120° ±1° for balanced loads.

 

120° ±3° for 50% unbalanced loads.

Voltage Imbalance:

 

20% Unbalanced Load

±1% from the arithmetic average of the 3 phases.

50% Unbalanced Load

±2% from the arithmetic average of the 3 phases.

Voltage Transient:

 

20% Load Step

±4% from the average peak voltage.

30% Load Step

±5% from the average peak voltage.

100% Load Step

±7% from the average peak voltage.

Loss or Return of AC Input Power

±1% from the average peak voltage.

Manual Transfer of 100% Load

±4% from the average peak voltage.

Voltage Transient Recovery Time:

To within 1% of steady state output voltage within 50 milliseconds.

 

 

Voltage Harmonic Content:

Maximum 5% RMS total, for any combination of linear and nonlinear loads.

 

Maximum 3% RMS single, for linear loads.

Module Overload Capacity at Full

104% of full load rating continuously.

Output Voltage:

125% of full load rating for 10 minutes.

(System overload capacity depends

150% of full load rating for 30 seconds.

on the configuration of on-line

(with ±2% voltage regulation).

modules.)

 

Fault Clearing:

300% of normal full load current subcycle.

 

1000% of normal full load current up to 40 milliseconds with bypass available.

Specifications and Ratings

121