17. To access the CPU315F 2PN/DP and later the frequency converter SINAMICS G120 by means
of Ethernet Online, the PG/PC interface has to be set to TCP/IP. This is done in the ’SIMATIC
Manager’ in the menu ’Options’, ’Set PG/PC interface’. ( SIMATIC Manager Extras
PG/PC Schnittstelle einstellen)
18. As interface, select TCP/IP with your network card. For example, ’TCP/IP -> Intel(R) PRO/100
VE Network Connection’ and accept with ’OK’. ( TCP/IP -> Intel(R) PRO/100 VE Network
Connection OK)
Note: A precondition for this is that the network card of the PC is configured correctly; for example,
IP address 192.168.0.99, Subnet 255.255.255.0 (refer to Module E02).