Automation and Drives - SCE
P0010 Startup Parameter Filter
Filters parameters, so that only parameters are selected that are assigned to a certain function group. For example, the parameters needed for quick startups are displayed according to their sequence.
The following settings are available
0:Ready
1:Quick startup
2:Converter
29:Download
30:Factory setting
•P0010 = 0
To start the converter, P0010 has to be reset to 0.
•P0010 = 1
The converter can be started up very quickly with the setting P0010 = 1. After that, only the most important parameters are visible (for example, P0304, P0305, etc.). The individual parameter values have to be entered successively.
The startup is completed and internal calculation is started by setting P3900 = 1 to 3. Then, the parameters P0010 and P3900 are automatically set to zero.
•P0010 = 2
Only for service purposes
•P0010 = 29
To transfer a parameter file by means of a PC tool (such as STARTER), the PC tool sets the parameter P0010 to 29. As soon as the data is downloaded, the PC tool resets the parameter P0010 to zero.
•P0010 = 30
If the parameters of the converter are reset, P0010 has to be set to 30.
The reset is started by setting P0970 = 1. The converter automatically resets all parameters to their factory setting. This can be of advantage if problems arise while parameters are configured, and the parameters have to be reconfigured. The reset to the factory settings takes approx. 60s.
Modifiable depending on the converter state
In addition,
For example, the parameter for quick startups P0010 (with the attribute "CT" in the parameter list) can be modified only in the quick startup "C" or in the ready mode "T"; not, however, in the "U" mode.
State |
| Description |
|
|
| |
|
|
|
|
|
| |
|
|
| Quick startup | |||
|
|
|
|
| ||
|
|
| Operation (drive is running) | |||
|
|
|
|
| ||
|
|
| Drive ready |