6.1.3The Main Setpoint (HSW)
Bit No.
The main setpoint is a 16 bit word that transmits the required frequency setpoint to the converter. The setpoint is transmitted as a signed integer
By means of the parameter P1082, the value 100% is normalized to a plant frequency. In this parameter, the frequency value is entered to which a setpoint of 100% is to correspond over the serial interface.
The output frequency is calculated as follows:
f = (HSW x P1082)/16384
6.1.4The Main Actual Value (HIW)
Bit No.
The main actual value is a 16 bit word that transmits the converter’s actual frequency output. The normalization of this value corresponds to that of the setpoint.
|
|
|
|
|
|
|