Automation and Drives - SCE

3.5.1.5Starting Performance of the SINAMICS G120

After the initial latching of the control unit onto the power module, the devices recognize each other. As an indication that the power module and the control unit were initially not identified, the message F0395 is displayed.

After confirming the message, you can begin with the startup.

For control units (CUs) without a failsafe function, F00395 is confirmed in one of the following ways:

By a reset to the factory setting

Using the function key FN on the BOP

Digital input or PLC signal “Acknowledge“ (depends on the setting of P0700)

Setting P7844 = 0

A standard power-up is a start after switching the unit on/off, or if power fails. It can be performed with or without the MMC.

Standard start without MMC

After a load cycle or a power failure, the converter copies the parameters from the EEPROM to the RAM.

Standard start with MMC

The CPU automatically recognizes the MMC. The power-up is controlled via P8458 as follows:

P8458 = 0: No automatic download of the parameters by the MMC.

P8458 = 1: One-time automatic download of parameters from the MMC (at the next power-up of the CPU (factory setting)). After the download, P8458 is set to 0 to prevent additional automatic parameter downloads.

P8458 = 2: Parameters are loaded automatically from the MMC (if present) after each power-up of the control unit.

The MMC can be removed after the download is completed. If no MMC is inserted, the converter powers up -without alarm indication or error message- with the parameters stored in the EEPROM, even if P8458 is set to 1 or 2.

 

Preface

Notes

Startup with PROFIBUS

Startup with PROFINET

Program Example

 

 

 

 

 

 

T I A Training Document

 

Page 48 of 147

 

Module

 

 

 

H01

 

 

Issued: 02/2008

 

Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET

Page 48
Image 48
Siemens manual Starting Performance of the Sinamics G120, Standard start without MMC, Standard start with MMC