Page | Robertson AP45 Autopilot |
| Installation |
The unit has separate mains supply for the autopilot electronics and the power unit (motor/solenoids). This reduces the interference to the autopilot electronics caused by the motor switching. The power unit supply cable (mains supply) should be of at least 4 mm2 (AWG10). The electronic supply cable should be 1,5 mm2 (AWG14).
Cables from control unit, rudder feedback unit, power unit and mains supply should be connected to the terminal blocks according to wiring diagram fig. 5.23. Sufficient free cable should be left inside the junction unit so that the P.C. board can be removed for repair without having to disconnect the cables from the terminal board.
Note!
The J45S Junction Unit has been set for 24V DC operation and prewired from factory to drive Robertson power units with solenoid valves such as RPU3 (solenoid supply is via J45S).
If the autopilot shall operate on 12 or 32V DC, set voltage selector
Check that the FB selector is in correct position
Run two voltage feed cables as follows:
Mains input for pump motor and solenoid valves is connected to + and - terminals marked "Supply" (Cable dimensions 4.0 mm2 - AWG10).
Autopilot (electronic) supply is connected to + and - terminals marked "Electronic" (Cable dimensions 1.5 mm2 - AWG14).
OTHER SOLENOID CONFIGURATIONS
(Driving steering gear solenoids not Robertson supplied).
If the "Supply" cable shall feed solenoid voltage only it may be reduced to 1.5mm2 - AWG14.
In installations where the unit shall operate solenoids with positive common, they must be connected according to Fig.
If the unit shall operate solenoids with negative common, they must be connected according to Fig.
Note!
(Does not apply for
Simrad Robertson AS
Egersund - Norway