Chapter 7. PARAMETER SETUP

No.

Item Code

Item

Factory

User

 

Setting

 

 

 

 

Setting

Setting

 

 

 

 

 

 

 

 

 

11

C

1 1

PID set auto-

0

 

0: OFF (PID set segment designation)

 

 

 

switching (CH1)

 

 

1: ON

 

 

 

 

 

 

 

[Note]

 

 

 

 

 

 

 

When set to 1, the PID set items in the program are

 

 

 

 

 

 

invalid.

 

 

 

 

 

 

 

The switching point for auto-switching is set in variable

 

 

 

 

 

 

parameters (C P . 1 1 to C P . 1 7).

 

 

 

 

 

 

 

 

12

C

1 2

MV setting at input 1

0

 

0: OFF

 

 

 

 

over-range (MV1)

 

 

1: ON

 

13

C

1 3

MV at input 1 over-

0

 

-10 to 110%

 

 

 

 

range (MV1)

 

 

[Note]

 

 

 

 

 

 

 

When C

1 2 setting is 0, “– – – –” is displayed and

 

 

 

 

 

 

setting is not possible.

14

C

1 4

Manual change

0

 

0: Bump-less

 

 

 

mode (MV1)

 

 

1: Preset

 

 

 

 

 

 

 

[Note]

 

 

 

 

 

 

 

When the programmer function is selected, operation

 

 

 

 

 

 

is bump-less regardless of the setting of C 1 4.

15

C 1 5

Preset manual value

0

 

-10 to 110%

 

 

 

 

(MV1)

 

 

[Note]

 

 

 

 

 

 

 

When C

1 4 setting is 0, “– – – –” is displayed and

 

 

 

 

 

 

setting is not possible.

 

 

 

 

 

 

 

 

16

C

1 6

MV in READY mode

0

 

-10 to 110%

 

 

 

 

(MV1, MV1 heat-

 

 

[Note]

 

 

 

 

cool output)

 

 

This setting is invalid even if the programmer function

 

 

 

 

 

 

is selected by C 1 8 setting.

 

 

 

 

 

 

On heat/cool models, this setting functions as the MV

 

 

 

 

 

 

(heat) setting in the READY mode.

 

 

 

 

 

 

 

 

17

C

1 7

MV (cool) in READY

0

 

-10 to 110%

 

 

 

 

mode (MV1 heat-

 

 

[Note]

 

 

 

 

cool output)

 

 

When the model is not a heat/cool model, “– – – –” is

 

 

 

 

 

 

displayed and setting is not possible.

 

 

 

 

 

 

 

18

C

1 8

Main output type

0

 

0: MV1 output (controller function)

 

 

 

(CH1)

 

 

1: SP1 output (programmer function)

 

 

 

 

 

 

[Note]

 

 

 

 

 

 

 

When the model is not a 5G output model, “– – – –” is

 

 

 

 

 

 

displayed and setting is not possible.

19

C 1 q

SP1 main output

0U

 

-1999 to 9999U

 

 

 

lower limit (4mA

 

 

[Note]

 

 

 

 

setting)

 

 

When the model is not a 5G output model and 8

 

 

 

 

 

 

setting is 0 on a 5G output model, “– – – –” is dis-

20

C 2 0

SP1 main output

1000U

 

played and setting is not possible.

 

 

 

upper limit (20mA

 

 

The relationship between the analog outputs and SP1

 

 

 

setting)

 

 

can be inverted by inverting the upper and lower limit

 

 

 

 

 

 

values.

 

21

C 2 1

Unused

 

[Note]

 

22

C 2 2

Unused

 

“– – – –” is displayed and setting is not possible.

23

C 2 3

Unused

 

 

 

24

C 2 4

Unused

 

 

 

25

C 2 5

Unused

 

 

 

26

C 2 6

Unused

 

 

 

27

C 2 7

Unused

 

 

 

28

C 2 8

Unused

 

 

 

29

C 2 q

Unused

 

 

 

30

C 3 0

Unused

 

 

 

7-28

Page 113
Image 113
Sonic Alert DCP301 user manual Parameters C P 1 to C P