Chapter 4. WIRING

4-8 Connecting control outputs (outputs 1, 2)

WARNING

Before wiring, or removing/mounting the DCP301, be sure to turn the power OFF. Failure to do so might cause electric shock.

Relay output (0D)

Connect as follows.

Load

Power supply

Handling Precautions

11

Contact rating, resistive load

125A (30Vdc/120Vac)

4A (240Vac)

13

Minimum switching current: 100mA

When switching small currents, connect a bleeder resistor to allow current flow of the minimum relay switching input (100mA min.).

Current output (5G)

Connect as follows.

Actuator

Handling Precautions

11

12

13

4 to 20/0 to 20mAdc Resistive load 600Ω max.

4 to 20mAdc and 0 to 20mAdc can be selected in setup data C 9 0.

Position-proportional output (2G)

Connect as follows paying attention to the switching direction.

2

Load 3

Open side

11

Contact rating

12

4A (120Vac, cosø =0.4)

Power supply Load 1

2A (240Vac, cosø =0.4)

Closed side

Y

Open

T

G

Closed

Handling Precautions

13

14

15

16

Feedback resistance 100 to 2500Ω

The life of internal relays is limited.

Avoid setting the PID constant in such a way that results in excessive repeated ON/OFF switching.

When using a 100/200Vac motor, pay attention to rush current and the contact rating. If necessary, provide an external auxiliary relay.

Separate the wiring for motor terminals (11) (12) (13) and feedback resistor terminals (14) (15) (16).

(Do not wire the leads in the same duct or use 6-core cable. Doing so might result in faulty controller operation caused by electrical noise when the motor is started up.)

When controlling without motor feedback with variable parameter M .-Cset to “2”, terminals (14) (15) (16) need not be connected.

4-9