Chapter 4. WIRING

3-wire system RS-485 mutual connection

Terminating resistor

Slave station DCP301 57 SDA

 

58 SDB

 

59 RDA

 

60 RDB

 

61 SG

 

FG

Master station

 

RDA

 

RDB

Shielded cable

 

SDA *

 

SDB

*

 

SG

 

FG

 

Shielded cable

Handling Precautions

Be sure to connect SG terminals each others.

Failure to do so might cause unstable communications.

Shielded cable

Terminating resistor

Slave station DCP301

57SDA

58SDB

59RDA

60RDB

61SG FG

Slave station DCP301

57SDA

58SDB

59RDA

60RDB

61SG FG

Provide terminating resistor of 150Ω± 5%, 1/2W min. at both ends of the communications path. Grounding of the shielded FG terminal should be carried out at only one end and not both ends. When there are only three RS-485 terminals, terminals marked * are wired internally.