Chapter 7. PARAMETER SETUP

Description of event configuration data

E D 1 (event 1 standby)

E D 2 (event 2 standby)

E D 3 (event 3 standby)

0:Standby OFF

1:Standby ON

When set to standby ON, event output becomes OFF if the controller is in the standby state even if the condition for turning event output ON is satisfied.

The controller enters the standby state in the following instances:

-When in the READY mode

-When shifting from the READY to the RUN mode

-When the power is turned ON

The standby state is canceled in the following instances:

-When the condition for turning event output OFF (not including the hysteresis pe- riod) is satisfied in one of the RUN, HOLD or FAST modes

-When set to standby OFF

In the following example, PV event direct, operating point 500° C, hysteresis 10° C and

standby ON are set. When the mode changes from READY to the RUN mode at PV 550° C, the controller enters the standby state, so event output is turned OFF.

Standby functions only when the event type is set to PV type event, and does not function when set to time event type or controller status type.

D L 1 (event 1 ON delay time)

D L 2 (event 2 ON delay time)

D L 3 (event 3 ON delay time)

The ON delay time is processed after completing all processes up to event output standby ON/OFF. Event output is turned ON when more than the ON delay time has elapsed with the condition for turning event output ON satisfied.

When the event type is set to ADV, the ON delay function does not operate whatever value is set as the ON delay time.

ON delay time is processed as follows.

Event OFF conditions

Event ON conditions

Event OFF conditions

 

Event output ON

 

Event output OFF

 

Event output OFF

 

ON delay time

Time

 

 