Chapter 6. OPERATION

6-4 External Switch (RSW) Operations

External switch (RSW) inputs

In all, the DCP301 is provided with 12 external switch inputs. Each of these inputs are differentiated by RSW1, RSW2 and so forth to RSW12. On models whose option 2 cata- log No. is “0”, only inputs RSW1 to RSW4 are mounted.

(RSW: external switch input)

External switch input types

The functions of RSW1 to 4, and RSW8 to 12 are fixed.

The functions of RSW5 to 7 are selected by the setup setting.

External

Function

Detection Method

Switch No.

 

 

 

 

 

 

 

RSW1

RUN

 

Rising edge

 

 

 

 

RSW2

HOLD

 

Rising edge

 

 

 

 

RSW3

RESET

 

Rising edge

 

 

 

 

RSW4

ADV

 

Rising edge

 

 

 

 

Selected by setup from the following functions

 

 

 

 

 

RSW5

FAST

 

Rising edge

 

 

 

 

RSW6

PV start

 

Rising edge

 

 

 

 

RSW7

AUTO/MANUAL

 

Rising/falling edge

 

 

 

 

 

AT start/stop

 

Rising/falling edge

 

 

 

 

G.Soak cancel by OR conditions

Status

 

 

 

 

G.Soak cancel by AND conditions

Status

 

 

 

 

Direct/reverse action switching

Status

 

 

 

 

RSW8

Program No. selection

Weighting 1

Status

 

 

 

 

RSW9

Program No. selection

Weighting 2

Status

 

 

 

 

RSW10

Program No. selection

Weighting 4

Status

 

 

 

 

RSW11

Program No. selection

Weighting 8

Status

 

 

 

 

RSW12

Program No. selection

Weighting 10

Status

 

 

 

 

With PV is valid only in the program operation mode and READY mode, and the PV start RUN mode is entered regardless of the PV start setting in the program. Note, however, that RUN mode is entered from the start point of the selected segment in READY mode when there is no SP for the PV start.

With G.Soak cancel by OR conditions, G.Soak standby is canceled when the external switch turns ON or when the PV enters the G.Soak width.

With G.Soak cancel by AND conditions, G.Soak standby is canceled when the exter- nal switch turns ON or when the PV enters the G.Soak width.

When the external switch turns ON by direct/reverse action switching, control opera- tion is the opposite to that set in setup parameter C 0 1. When the external switch turned OFF, control operation is that set in setup parameter C 0 1.