Chapter 7. PARAMETER SETUP

Description of variable parameter settings

L O C (key lock)

0:Key lock disabled

1:Display of setup data settings disabled

2:Display of parameter settings and program settings disabled

3:Use of operation keys disabled

4:Display of parameter settings and program settings displayed, and use of operation keys disabled

When L O C is set to 1, the following keys are disabled.

 

Basic display state:

FUNC

+

CLR + DISP

(general reset)

 

Only S E T can be selected by setting group selection in the parameter setup state.

When L O C is set to 2, the following keys are disabled.

 

Basic display state:

FUNC

+

PROG

(program setup)

 

 

 

+

PROG

(program copy)

 

 

FUNC + CLR + DISP

(general reset)

 

Only P A R A can be selected by setting group selection in the parameter setup state.

 

However, note that items assigned to PARA

can be called up by PARA in the basic dis-

 

play state.

 

 

 

 

When L O C is set to 3, the following keys are disabled.

 

Basic display state:

PROG

 

 

(program selection)

 

 

 

 

 

 

 

 

 

(program selection)

 

 

RUN/HOLD

 

 

(RUN, HOLD)

 

 

PROG

+ RUN/HOLD

(RESET)

 

 

PROG

+ DISP

(ADV)

 

 

FUNC

+

 

(FAST)

 

 

A/M

 

 

(AUTO, MANUAL)

 

 

 

 

 

 

 

AT

 

 

(AT start, AT cancel)

 

 

 

 

 

 

 

FUNC + CLR + DISP

(general reset)

 

However, note that MV (when controller functions are selected) and SP (when pro-

 

grammer functions are selected) can be changed in the basic display state in the

 

MANUAL mode.

 

 

 

 

When L O C is set to 4, all keys disabled when L O C is set to 2 and 3 are disabled.

P R T C (program protect)

0:Changing program settings enabled

1:Changing program settings disabled

When P R T C is set to 1, the following keys are disabled.

Basic display state:

 

+

PROG

(program copy)

 

FUNC +

CLR + DISP

(general reset)

Program setup state:

ENT

 

 

(start of value entry)

 

 

 

 

FUNC

+

ENT

(segment insert/delete)

7-10

Page 95
Image 95
Sonic Alert DCP301 user manual Description of variable parameter settings, C key lock, T C program protect