Chapter 6. OPERATION

Read timing

Timing of RSW1 to 7

Inputs RSW1 to RSW7 are read according to the following timing.

(1)When input changes state from OFF to ON, the time from the change up to reading is 0.2s max.

(2)When input changes state from ON to OFF, the time from the change up to reading is 0.2s max.

External switch input state

OFF read

(1)

(2)

Timing of RSW8 to 12, RUN and PV start

The time from the change in input state up to reading when selecting program Nos. by RSW8 to RSW12 is 0.4s max.

Accordingly, due to the relationship with RUN operation, be sure to observe timings to (4) in the following diagram.

PV start operation also must conform to RUN operation.

(1)The time from fixing of the selected No. up to the rising edge of the RUN signal is 0.4s min.

(2)The time from the rising edge of the RUN signal up to holding of the program No. is 0.2s min.

(3)The time from holding of RUN signal OFF up to the rising edge of the RUN signal is 0.2s min.

(4)The time from the rising edge of the RUN signal up to holding of RUN signal ON is 0.2s min.

(5)The time from fixing of the selected No. up to changing of the program No. is 0.4s max.

(6)The time from the rising edge of the RUN signal up to start of RUN is 0.4s max.

Program selection No.

State of No. different

State of

State of No. di

(5 inputs)

from that selected

selected No.

from that selec

(1)

(2)

RUN signal

(3)

(4)

(5)

(6)

Program No. No. different from that selected

Selected No.

Handling Precautions

When operating the controller by external switch inputs, operation can be carried out more reliably if a margin is added to the minimum time for the above read times.

6-10