Chapter 7. PARAMETER SETUP

7-3 Parameter Setup List

Note “U” and “%FS” used in the “Factory Setting” and “Setting” columns in the table mean the following:

U:The decimal point changes according to the input range type setting. For example, when one digit past the decimal point is allowed, -1999U becomes 199.9, and 9999U becomes 999.9.

%FS: The numbers and decimal point position changes according to the input range setting.

For example, when the input range is 0.0 to 800.0° C, 0%FS is 0.0 and 100%FS is 800.0.

Variable parameter settings “P A R A

No.

Item Code

Item

Factory

User

 

Setting

 

 

 

Setting

Setting

 

 

 

 

 

 

 

 

1

L O C

Key lock

0

 

0: Key lock disabled

 

 

 

 

 

1: Display of setup data settings disabled

 

 

 

 

 

2: Display of parameter settings and program settings

 

 

 

 

 

 

disabled

 

 

 

 

 

3: Use of operation keys disabled

 

 

 

 

 

4: Display of parameter settings and program settings

 

 

 

 

 

 

displayed, and use of operation keys disabled

 

 

 

 

 

[Note]

 

 

 

 

 

 

Two or more key lock setting values for actual key lock

 

 

 

 

 

 

items and items assigned to PARA can be displayed

 

 

 

 

 

 

and set.

2

P R T C

Program protect

0

 

0: Changing program settings enabled

 

 

 

 

 

1: Changing program settings disabled

3

F L

Input 1 digital filter

0.0

 

0.0 to 120.0s

 

 

 

 

 

[Note]

 

 

 

 

 

 

0.0 disables the filter.

4

P B 1

Input 1 bias

0U

 

-1000 to 1000U

5

S B 1

SP1 bias

0U

 

-1999 to 9999U

6

O T L

MV change limitter

0.0

 

0.0 to 10.0% (0.1%s steps)

 

 

(CH1)

 

 

[Note]

 

 

 

 

 

 

0.0 disables the limit.

7

1 O U T

PID operation initial

0.0

 

0.0 to 100%

 

 

MV (CH1)

(50.0)

 

[Note]

 

 

 

 

 

On heat/cool models, the factory setting is 50.0.

 

 

 

 

 

 

8

R P 1 D

PID operation

0

 

0: Automatic judgment of initialization is carried out by

 

 

initialization

 

 

 

advance operation.

 

 

 

 

 

1: Initialization is carried out by advance operation.

 

 

 

 

 

2: Initialization is not carried out by advance operation.

9

A T

Auto-tuning method

0

 

0: AT is disabled.

 

 

selection (CH1)

 

 

1: General AT is executed.

 

 

 

 

 

2: Overshoot-inhibited AT is executed.

 

 

 

 

 

3: AT by neural net is executed.

 

 

 

 

 

[Note]

 

 

 

 

 

 

On heat/cool models, “– – – –” is displayed, and

 

 

 

 

 

 

setting is not possible.

10

S T

Smart-tuning

0

 

0: Smart-tuning is disabled.

 

 

method selection

 

 

1: The brake value is fixed to inhibit overshoot.

 

 

(CH1)

 

 

2: Overshoot is inhibited while automatically reviewing

 

 

 

 

 

 

the brake value.

 

 

 

 

 

[Note]

 

 

 

 

 

 

On heat/cool models, “– – – –” is displayed, and

 

 

 

 

 

 

setting is not possible.

11

2 P 1 D

Advanced PID

0

 

0:

2 degrees of freedom PID is disabled.

 

 

selection (CH1)

 

 

1:

2 degrees of freedom PID is enabled.

 

 

 

 

 

[Note]

 

 

 

 

 

 

On heat/cool models, “– – – –” is displayed, and

 

 

 

 

 

 

setting is not possible.