SAFETY REQUIREMENTS

EN2I-6026

To reduce risk of electric shock which could cause personal injury, all safety notices in this documentation.

This symbol warns the user of a potential shock hazard where hazardous live voltages may be accessible.

If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment must be impaired.

Do not replace any component (or part) not explicity specified as replaceable by your supplier.

All wiring must be in accordance with local norms and carried out by authorized experienced personnel.

The ground terminal must be connected before any other wiring (and disconnected last).

A switch in the main supply is required near the equipment.

Mains power supply wiring requires a (T) 1.0A, 250V fuse(s).(IEC127)

EQUIPMENT RATINGS

 

Supply voltages

100 to 240Vac (operation power voltages 90 to 264Vac)

Frequency

50/60Hz

Power or current ratings

30VA maximum

EQUIPMENT CONDITIONS

Do not operate the instrument in the presence of flammable liquids or vapors. Operation of any electrical instrument in such an environment constitutes a safety hazard.

Temperature

0 to 50

 

Humidity

10 to 90%RH

Vibration

Frequency

10 to 60Hz

 

Acceleration

1.96m/s2 maximum

Installation category

Category II (IEC664-1, EN61010-1)

Pollution degree

2

 

EQUIPMENT INSTALLATION

The controller must be mounted into a panel to limit operator access to the rear terminal. Specification of common mode voltage; The common mode voltages of all I/O except for main supply and relay outputs are less than 30Vrms, 42.4V peak and 60Vdc.

APPLICABLE STANDARDS

EN61010-1, EN50081-2, EN50082-2, EN61326

CAUTION

Danger of explosion if battery is incorrectly replaced.

Replace only with the same or equivalent type recommended by the manufacturer.

Dispose of used batterries according to the manufacturer’s instructions.