Chapter 7. PARAMETER SETUP

No.

Item Code

Item

Factory

User

Setting

 

 

 

Setting

Setting

 

 

 

 

 

 

 

29

M .-C

Motor control

0

 

0: MFB control (conventional) + estimated position

 

 

method selection

 

 

control

 

 

 

 

 

1: MFB control (conventional) only

 

 

 

 

 

2: Estimated position control only

 

 

 

 

 

[Note]

 

 

 

 

 

On models other than 2G output models, “– – – –” is

 

 

 

 

 

displayed and setting is not possible.

30

M .-A T

Motor valve opening

0

 

0: Adjustment disabled

 

 

automatic adjust-

 

 

1: Adjustment enabled

 

 

ment

 

 

[Note]

 

 

 

 

 

On models other than 2G output models, “– – – –” is

 

 

 

 

 

displayed and setting is not possible.

 

 

 

 

 

On 2G output models, when M .-Csetting is 2, “– – – –

 

 

 

 

 

” is displayed and setting is not possible.

 

 

 

 

 

 

31

M .-C L

Motor valve opening

1000

 

0 to (fully open adjustment - 500)

 

 

adjustment fully

 

 

[Note]

 

 

closed position

 

 

On models other than 2G output models, “– – – –” is

 

 

 

 

 

displayed and setting is not possible.

 

 

 

 

 

On 2G output models, when M .-Csetting is 2, “– – – –

 

 

 

 

 

” is displayed and setting is not possible.

32

M .-O P

Motor valve opening

9000

 

(fully closed adjustment + 500) to 9999

 

 

adjustment fully

 

 

[Note]

 

 

open position

 

 

On models other than 2G output models, “– – – –” is

 

 

 

 

 

displayed and setting is not possible.

 

 

 

 

 

On 2G output models, when M .-Csetting is 2, “– – – –

 

 

 

 

 

” is displayed and setting is not possible.

33

M .-T

Motor valve opening

30.0

 

5.0 to 240.0s

 

 

adjustment fully

 

 

[Note]

 

 

open/closed time

 

 

On models other than 2G output models, “– – – –” is

 

 

 

 

 

displayed and setting is not possible.