Chapter 7. PARAMETER SETUP

No.

Item Code

Item

Factory

User

 

 

 

 

 

Setting

 

 

 

Setting

Setting

 

 

 

 

 

 

 

 

 

 

 

 

 

21

P -3

Proportional band

100.0

 

When variable parameter 2 P 1 D setting is 1 (2

 

 

(PID set 3)

 

 

 

degrees of freedom PID enabled), the parameter (P, 1,

22

1 -3

Reset time

0

 

 

D) ideal for control when SP changes and the param-

 

 

(PID set 3)

 

 

 

eter (D P, D 1, D D) ideal for inhibiting disturbance

23

D -3

Rate time

0

 

 

during settling are automatically switched.

 

 

(PID set 3)

 

 

 

 

 

 

 

 

24

O L -3

MV lower limit

0.0

 

Decreasing the proportional band (P, D P) value

 

 

(PID set 3)

 

 

 

improves controllability. However, it also makes

25

O H -3

MV upper limit

100.0

 

 

overshoot or hunting more likely to occur.

 

 

(PID set 3)

 

 

 

Use of the controller on a motor or actuator shortens

26

R E -3

Manual reset

50.0

 

 

 

 

the controller’s life. Do not set the proportional band

 

 

(PID set 3)

 

 

 

(P, D P) to too small a value.

27

B R -3

Brake

0

 

 

 

 

 

 

 

 

 

(PID set 3)

 

 

Decreasing the reset time (1, D 1) improves trackability.

28

D P -3

Disturbance inhibit

100.0

 

 

However, it also makes cycling caused by integrating

 

 

proportional band

 

 

 

action more likely to occur.

 

 

(PID set 3)

 

 

 

 

 

 

 

 

When 1 setting is 0, integrating operation for inhibiting

29

D I -3

Disturbance inhibit

120

 

 

disturbance also functions.

 

 

reset time

 

 

 

 

 

 

 

 

 

 

(PID set 3)

 

 

Increasing the rate time (D, D D) allows overshoot to

30

D D -3

Disturbance inhibit

0

 

 

be inhibited more easily. However, it also make

 

 

rate time

 

 

 

hunting more likely to occur as the controller reacts to

 

 

(PID set 3)

 

 

 

minute changes in PV.

31

P -4

Proportional band

100.0

 

 

In a temperature control system, setting the rate time

 

 

(PID set 4)

 

 

 

 

 

 

 

 

to 1/

 

to 1/

 

of the integrating time is generally consid-

32

1 -4

Reset time

0

 

 

3

4

 

 

ered to be appropriate. In a pressure or flow rate

 

 

(PID set 4)

 

 

 

 

 

 

 

 

control system, derivative action causes hunting.

33

D -4

Rate time

0

 

 

 

 

Either set the D setting to 0.0 to disable derivative

 

 

(PID set 4)

 

 

 

 

 

 

 

 

action, or decrease the setting so that derivative action

34

O L -4

MV lower limit

0.0

 

 

 

 

is almost negligible. The latter solution is more

 

 

(PID set 4)

 

 

 

 

 

 

 

 

frequently adopted.

35

O H -4

MV upper limit

100.0

 

 

 

 

 

 

 

 

 

 

 

(PID set 4)

 

 

The MV upper and lower limits (O L, O H) function as

36

R E -4

Manual reset

50.0

 

 

 

integrating limits. When the MV reaches the upper or

 

 

(PID set 4)

 

 

 

 

 

 

 

 

lower limit, integration no longer functions. This

37

B R -4

Brake

0

 

 

 

 

prevents reset wind-up that occurs when the PV has

 

 

(PID set 4)

 

 

 

 

 

 

 

 

not risen for a long time.

38

D P -4

Disturbance inhibit

100.0

 

 

 

 

 

 

 

 

 

 

 

proportional band

 

 

Manual reset (R E) is a setting for eliminating offset

 

 

(PID set 4)

 

 

 

 

 

 

 

that occurs during proportional action (integrated

39

D 1 -4

Disturbance inhibit

120

 

 

 

 

action disabled). For manual reset, set the MV ideal for

 

 

reset time

 

 

 

 

 

 

 

 

deviation 0.

 

 

(PID set 4)

 

 

 

 

 

 

 

 

 

 

 

 

 

40

D D -4

Disturbance inhibit

0

 

Increasing the brake (B R) value increases the

 

 

rate time

 

 

 

overshoot inhibit effect. However, it also lengthens the

 

 

(PID set 4)

 

 

 

rise time.

 

 

 

 

 

 

 

 

 

 

 

 

 

7-24