Chapter 7. PARAMETER SETUP

Note 1) On heat/cool models, this sets how the relationship between heat-side output and cool-side output should be processed with respect to the MV resulting from PID operation.

Dead zone<0

Dead zone=0

100%

 

 

100%

 

 

Dead

 

 

 

Control output

zone

 

 

 

 

 

 

 

values

Output

Output

Output

Output

 

0%

(cool)

(heat)

(cool)

(heat)

 

MV

0%

MV

 

 

 

 

50%

100%

50%

100%

Dead zone>0

100%

 

Dead

 

zone

 

Output

Output

(cool)

(heat)

0%

MV

 

50%

100%

Note 2) Constants OL and OH function as follows:

100%

Cool-side OH

Heat-side OL 0%

Cool-side

Heat-side

output

output

Heat-side OH

 

 

Cool-side OL

 

 

MV

50%

 

100%

Note 3) When MV 50%, the heat-side PID set is switched to. When MV < 50%, the cool-side PID set is switched to.

Note 4) PID set selection is carried out by setting value and external switch.