Chapter 4. WIRING

4-9 Connecting auxiliary outputs (outputs 2, 3)

Optional auxiliary outputs can be added on.

WARNING

Before wiring, or removing/mounting the DCP301, be sure to turn the power OFF. Failure to do so might cause electric shock.

0D, 5G, 6D auxiliary outputs

Receiver

Receiver

14

15

16

17

18

19

Auxiliary output 1 (output 2)

4 to 20/0 to 20mAdc Resistive load 600max.

Auxiliary output 2 (output 3)

4 to 20/0 to 20mAdc Resistive load 600max.

Handling Precautions

4 to 20mAdc and 0 to 20mAdc can be selected in setup data C 9 0.

Use shielded cable only.

2G, 3D, 5K auxiliary outputs

Receiver

17

18

19

Auxiliary output 2 (output 3)

4 to 20/0 to 20mAdc Resistive load 600max.

Auxiliary output 1 is not provided for 2G, 3D and 5K outputs.

Handling Precautions

4 to 20mAdc and 0 to 20mAdc can be selected in setup data C 9 0.

Use shielded cable only.

4-11

Page 43
Image 43
Sonic Alert DCP301 Connecting auxiliary outputs outputs 2, 0D, 5G, 6D auxiliary outputs, 2G, 3D, 5K auxiliary outputs