Chapter 7. PARAMETER SETUP

7-27

Setup data settings S E t
No. Item Code Item Factory User Setting
Setting Setting
1C 0 10
2C 0 20
3C 0 30
4C 0 4Not fixed
5C 0 5Not fixed
6C 0 6Not fixed
7C 0 70.0
8C 0 80
9C 0 q0%FS
10 C 1 0100%FS
0: Reverse action (heat)
1: Direct action (cool)
[Note]
On heat/cool models, “– – – –” is displayed and setting
is not possible.
On other models, external switch input can invert
direct/reverse action on the setting of C 0 1.
0: °C
1: °F
[Note]
When the input 1 range type is linear, “– – – –” is
displayed and setting is not possible.
0 to 73
0 to 20: Thermocouple
32 to 40, 48 to 56: Resistance temperature detector
64 to 73: Linear (dc current, dc voltage)
[Note]
Refer to the input 1 range table. Operation according
to a setting not listed in this table is not fixed.
0 to 3
[Note]
When the input 1 range type is non-linear, “– – – –” is
displayed and setting is not possible.
When the input 1 range type is changed from non-
linear to linear, the original non-linear range values
remain.
-1999 to 9999U
[Note]
When the input 1 range type is non-linear, “– – – –” is
displayed and setting is not possible.
When the input 1 range type is changed from non-
linear to linear, the original non-linear range values
remain.
The relationship between the analog inputs and
readout values can be inverted by inverting the upper
and lower limit values.
0.0 to 10.0% (ratio to input range)
[Note]
0.0 disables square root extraction.
When the input 1 range type is non-linear, “– – – –” is
displayed and setting is not possible.
0: Disabled
1: Enabled
[Note]
Table data setting (a, b) is used for the linearization
table.
-1999 to upper limit U
[Note]
Changing the input 1 range has no effect on the range.
However, note that a general reset sets the range to
the 0%FS value of the input 1 range.
Lower limit to 9999U
[Note]
Changing the input 1 range has no effect on the range.
However, note that a general reset sets the range to
the 0%FS value of the input 1 range.
Control action (CH1)
Input 1 temperature
unit
Input 1 range type
Input 1 range
decimal point
position
Input 1 range lower
limit (0%)
Input 1 range upper
limit (100%)
Input 1 root extrac-
tion dropout
Input 1 linearization
table approximation
SP1 lower limit
SP1 upper limit