Chapter 7. PARAMETER SETUP

Setup data settings “S E t

No.

Item Code

Item

Factory

User

Setting

 

 

 

Setting

Setting

 

 

 

 

 

 

 

1

C 0 1

Control action (CH1)

0

 

0: Reverse action (heat)

 

 

 

 

 

1: Direct action (cool)

 

 

 

 

 

[Note]

 

 

 

 

 

On heat/cool models, “– – – –” is displayed and setting

 

 

 

 

 

is not possible.

 

 

 

 

 

On other models, external switch input can invert

 

 

 

 

 

direct/reverse action on the setting of C 0 1.

 

 

 

 

 

 

2

C 0 2

Input 1 temperature

0

 

0: ° C

 

 

unit

 

 

1: ° F

 

 

 

 

 

[Note]

 

 

 

 

 

When the input 1 range type is linear, “– – – –” is

 

 

 

 

 

displayed and setting is not possible.

3

C 0 3

Input 1 range type

0

 

0 to 73

 

 

 

 

 

0 to 20: Thermocouple

 

 

 

 

 

32 to 40, 48 to 56: Resistance temperature detector

 

 

 

 

 

64 to 73: Linear (dc current, dc voltage)

 

 

 

 

 

[Note]

 

 

 

 

 

Refer to the input 1 range table. Operation according

 

 

 

 

 

to a setting not listed in this table is not fixed.

4

C 0 4

Input 1 range

Not fixed

 

0 to 3

 

 

decimal point

 

 

[Note]

 

 

position

 

 

When the input 1 range type is non-linear, “– – – –” is

 

 

 

 

 

displayed and setting is not possible.

 

 

 

 

 

When the input 1 range type is changed from non-

 

 

 

 

 

linear to linear, the original non-linear range values

 

 

 

 

 

remain.

5

C 0 5

Input 1 range lower

Not fixed

 

-1999 to 9999U

 

 

limit (0%)

 

 

[Note]

 

 

 

 

 

When the input 1 range type is non-linear, “– – – –” is

6

C 0 6

Input 1 range upper

Not fixed

 

displayed and setting is not possible.

 

 

limit (100%)

 

 

When the input 1 range type is changed from non-

 

 

 

 

 

linear to linear, the original non-linear range values

 

 

 

 

 

remain.

 

 

 

 

 

The relationship between the analog inputs and

 

 

 

 

 

readout values can be inverted by inverting the upper

 

 

 

 

 

and lower limit values.

7

C 0 7

Input 1 root extrac-

0.0

 

0.0 to 10.0% (ratio to input range)

 

 

tion dropout

 

 

[Note]

 

 

 

 

 

0.0 disables square root extraction.

 

 

 

 

 

When the input 1 range type is non-linear, “– – – –” is

 

 

 

 

 

displayed and setting is not possible.

8

C 0 8

Input 1 linearization

0

 

0: Disabled

 

 

table approximation

 

 

1: Enabled

 

 

 

 

 

[Note]

 

 

 

 

 

Table data setting (a, b) is used for the linearization

 

 

 

 

 

table.

9

C 0 q

SP1 lower limit

0%FS

 

-1999 to upper limit U

 

 

 

 

 

[Note]

 

 

 

 

 

Changing the input 1 range has no effect on the range.

 

 

 

 

 

However, note that a general reset sets the range to

 

 

 

 

 

the 0%FS value of the input 1 range.

 

 

 

 

 

 

10

C 1 0

SP1 upper limit

100%FS

 

Lower limit to 9999U

 

 

 

 

 

[Note]

 

 

 

 

 

Changing the input 1 range has no effect on the range.

 

 

 

 

 

However, note that a general reset sets the range to

 

 

 

 

 

the 0%FS value of the input 1 range.

 

 

 

 

 

 

7-27

Page 112
Image 112