Sonic Alert DCP301 user manual Parameter Setup

Models: DCP301

1 187
Download 187 pages 24.41 Kb
Page 105
Image 105

Chapter 7. PARAMETER SETUP

No.

Item Code

Item

Factory

User

 

Setting

 

 

 

Setting

Setting

 

 

 

 

 

 

 

 

9

E T 3

Event 3 type

0

 

PV type events

 

 

 

 

 

0: PV direct

 

 

 

 

 

1: PV reverse

 

 

 

 

 

2: Deviation direct

 

 

 

 

 

3: Deviation reverse

 

 

 

 

 

4: Absolute value deviation1 direct

 

 

 

 

 

5: Absolute value deviation1 reverse

 

 

 

 

 

6: SP direct

 

 

 

 

 

7: SP reverse

 

 

 

 

 

8: MV direct

 

 

 

 

 

9: MV reverse

 

 

 

 

 

10: MFB direct

 

 

 

 

 

11: MFB reverse

 

 

 

 

 

12 to 49: NOP

 

 

 

 

 

Time events

 

 

 

 

 

50: Time event

 

 

 

 

 

51 to 99: NOP

 

 

 

 

 

Controller status events

 

 

 

 

 

100: RUN+HOLD+FAST+END

 

 

 

 

 

101: READY

 

 

 

 

 

102: RUN

 

 

 

 

 

103: HOLD

 

 

 

 

 

104:

FAST

 

 

 

 

 

105:

END

 

 

 

 

 

106:

G.Soak standby

 

 

 

 

 

107: MANUAL

 

 

 

 

 

108: Auto-tuning executing

 

 

 

 

 

109: Constant-value operation

 

 

 

 

 

110: MFB estimated position control

 

 

 

 

 

111: Sum of all alarms

 

 

 

 

 

112:

PV range alarm

 

 

 

 

 

113:

Controller alarm

 

 

 

 

 

114:

Low battery voltage

 

 

 

 

 

115: Console setup in progress

 

 

 

 

 

116: Loader setup in progress

 

 

 

 

 

117: ADV (ON time 1s)

 

 

 

 

 

118 to 199: NOP

 

 

 

 

 

[Note]

 

 

 

 

 

 

Setting can be changed only in READY mode.

10

E D 3

Event 3 standby

0

 

0: Standby OFF

 

 

 

 

 

1: Standby ON

 

 

 

 

 

[Note]

 

 

 

 

 

 

The controller stands by after power is restored and in

 

 

 

 

 

the READY mode. When the event type setting is 50,

 

 

 

 

 

“– – – –” is displayed and setting is not possible.

11

H Y S 3

Event 3 hysteresis

5

 

0 to 200U (when event type is neither MV nor MFB)

 

 

 

 

 

0.0 to 20.0% (when event type is MV or MFB)

 

 

 

 

 

[Note]

 

 

 

 

 

 

When the event type setting is 50, “– – – –” is

 

 

 

 

 

displayed and setting is not possible.

 

 

 

 

 

 

12

D L 3

Event 3 ON delay

0

 

0 to 3600s

 

 

time

 

 

 

 

 

 

 

 

 

 

 

7-20

Page 105
Image 105
Sonic Alert DCP301 user manual Parameter Setup