Chapter 7. PARAMETER SETUP

Constant-value operation data settings “C N S t

No.

Item Code

Item

Factory

User

 

 

 

Setting

 

 

 

Setting

Setting

 

 

 

 

 

 

 

 

 

 

1

M .O D E

Operation mode

0

 

0: Program operation

 

 

 

 

 

1: Constant-value operation

 

 

 

 

 

[Note]

 

 

 

 

 

 

 

 

This setting can be changed only in the READY mode.

2

S P

SP1

0

 

This setting can be set in the SP1 lower to upper limit

 

 

 

 

 

range in setup data settings C 0 q and C 1 0.

 

 

 

 

 

 

 

 

3

S P 2

Unused

0

 

[Note]

 

 

 

 

 

 

 

 

“– – – –” is displayed and setting is not possible.

 

 

 

 

 

 

 

4

E V 1

Event 1 setting

9999

 

-1999 to 9999U

(event type is deviation or SP)

 

 

value

 

 

0 to 9999U

(event type is absolute value deviation)

5

E V 2

Event 2 setting

9999

 

-10.0 to 110.0% (event type is MV or MFB)

 

 

value

 

 

[Note]

 

 

6

E V 3

Event 3 setting

9999

 

 

When the event configuration data type setting is 50

 

 

value

 

 

 

for each event, “– – – –” is displayed and setting is not

 

 

 

 

 

 

possible.

 

 

 

 

 

 

 

 

 

7

Unused

 

[Note]

 

 

8

Unused

 

 

“– – – –” is displayed and setting is not possible.

9

Unused

 

 

 

 

 

10

Unused

 

 

 

 

 

11

P .

Proportional band

100.0

 

P

 

: 0.0 to 999.9% (0D, 6D output models)

 

 

(CH1)

 

 

 

 

0.0 enables ON-OFF control.

12

I .

Reset time (CH1)

0

 

 

 

0.1 to 999.9% (models other than 0D and 6D

13

D .

Rate time (CH1)

0

 

 

 

models)

 

14

O L .

MV lower limit (CH1)

0.0

 

I

 

: 0 to 3600s

15

O H .

MV upper limit (CH1)

100.0

 

 

 

0 disables integral action.

16

R E .

Manual reset (CH1)

50.0

 

D

 

: 0 to 1200s

17

B R .

Brake (CH1)

0

 

 

 

0 disables derivative action.

18

D P .

Disturbance inhibit

100.0

 

O L : -10.0 to MV upper limit %

 

 

proportional band

 

 

O H : MV lower limit to 110.0%

 

 

(CH1)

 

 

R E : 0.0 to 100.0%

19

D I .

Disturbance inhibit

120

 

B R : 0 to 30

 

 

 

reset time (CH1)

 

 

 

 

0 disables the brake function.

20

D D .

Disturbance inhibit

0

 

D P

: 0.1 to 999.9%

 

 

rate time (CH1)

 

 

D

I

: 1 to 3600s

21

P .-C

Proportional band

100.0

 

D D : 0 to 1200

 

 

 

(for cool control)

 

 

 

 

0 disables derivative action.

22

I .-C

Reset time (CH1)

0

 

 

 

 

 

 

 

(for cool control)

 

 

[Note]

 

 

23

D .-C

Rate time (CH1) (for

0

 

On 0D and 6D output models, when P setting is 0.0,

 

 

cool control)

 

 

 

ON-OFF control is enabled. “– – – –” is displayed for

24

O L .-C

MV lower limit (CH1)

0.0

 

 

items I, D, O L, O H, R E, D P, D I and D D, and

 

 

(for cool control)

 

 

 

setting is not possible.

25

O H .-C

MV upper limit (CH1)

100.0

 

When variable parameter M .-Csetting is 2 (estimated

 

 

(for cool control)

 

 

 

position control only) on 2G output models, “– – – –” is

26

R E .-C

Manual reset (CH1)

50.0

 

 

displayed for items OL and OH, and setting is not

 

 

(for cool control)

 

 

 

possible.

 

 

 

 

 

 

When I setting is not 0, “– – – –” is displayed for R E

 

 

 

 

 

 

and setting is not possible.

 

 

 

 

 

When variable parameter S T setting is 0 (smart-tuning

 

 

 

 

 

 

disabled), “– – – –” is displayed for B R and setting is

 

 

 

 

 

 

not possible.

 

 

 

 

 

 

When variable parameter 2 P I D setting is 0 (2

 

 

 

 

 

 

degrees of freedom PID disabled), the items for D P,

 

 

 

 

 

 

D I, D D are not displayed.

 

 

 

 

 

 

For details, see the Note for PID parameters.

27

Unused

 

[Note]

 

 

28

Unused

 

 

“– – – –” is displayed and setting is not possible.

29

Unused

 

 

 

 

 

30

Unused

 

 

 

 

 

7-42