Chapter 5. FUNCTIONS

If the ON time is set to 0 in the case of G.Soak standby, output becomes ON from the G.Soak standby state, and the ON time is started at completion of the G.Soak standby time.

The output time = G.Soak time + OFF time (See segment 8 in the figure.)

ON and OFF time settings the same time as the segment end point are valid in the case of the final segment END mode.

(See segment 10 in the figure.)

Segment

 

8

 

 

 

 

 

 

 

ON time

G.Soak standby

 

 

Segment 8 time start

 

 

 

When 0N=0, output turns

OFF time ON when there is input to

segment 8.

Output ON

Output OFF

Segment

9

ON time

ON=segment time

OFF time

 

Output ON

 

Output OFF

 

Segment

10

ON time

 

Segment time

 

 

END mode

 

ON=segment time

 

 

 

 

 

 

OFF time

Output ON

Output OFF

Segment No. events

The current segment No. is output as binary code.

When all of T1 to T5 are selected as segment No. events in the time event type setup, all ON-OFF operations are as shown in the following table.

When T1 to T4 are assigned in part to segment No. events, only the assigned time events operate as shown in the following table, and the remaining events operate as regular time events.

Segment

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

Event No.

No.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T1

 

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T2

 

OFF

ON

ON

OFF

OFF

ON

ON

OFF

OFF

ON

ON

OFF

OFF

ON

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T3

 

OFF

OFF

OFF

ON

ON

ON

ON

OFF

OFF

OFF

OFF

ON

ON

ON

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T4

 

OFF

OFF

OFF

OFF

OFF

OFF

OFF

ON

ON

ON

ON

ON

ON

ON

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T5

 

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Segment

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

Event No.

No.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T1

 

OFF

ON OFF

ON

OFF

ON OFF

ON

OFF

ON

OFF

ON

OFF

ON OFF

T2

 

OFF OFF

ON

ON

OFF OFF

ON

ON

OFF OFF

ON

ON

OFF OFF

ON

T3

 

OFF OFF

OFF OFF ON ON ON

ON OFF OFF OFF OFF

ON

ON

ON

T4

 

OFF OFF

OFF OFF OFF OFF OFF OFF

ON

ON

ON

ON

ON

ON

ON

T5

 

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

5-7

Page 58
Image 58
Sonic Alert DCP301 user manual Segment No. events