Chapter 4. WIRING

5-wire system RS-485 mutual connection

Terminating resistor

Terminating resistor

Shielded cable

Master station

RDA

RDB

SDA

SDB

SG

FG

Shielded cable

Handling Precautions

Be sure to connect SG terminals each others.

Failure to do so might cause unstable communications.

Shielded cable

Terminating resistor

Terminating resistor

Slave station DCP301

57SDA

58SDB

59RDA

60RDB

61SG FG

Slave station DCP301

57SDA

58SDB

59RDA

60RDB

61SG FG

Slave station DCP301

57SDA

58SDB

59RDA

60RDB

61SG FG

Provide terminating resistor of 150Ω± 5%, 1/2W min. at both ends of the communications path. Grounding of the shielded FG terminal should be carried out at only one end and not both ends.

4-17

Page 49
Image 49
Sonic Alert DCP301 user manual Wire system RS-485 mutual connection