Chapter 11. CALIBRATION

PV calibration

Scroll , , , or keys to show (1.0.1.1.) on upper display, then press ENT

key.

Gain No. select

Press PARA key until the PROG/SEG display shows (01-01). Connect calibration device (See Section 11-3 Set Up”).

Input the gain number (See Table 11-9 and Table 11-10) by scrolling , , , or keys the upper display ( ENT key not required).

PV zero, span

(1)PV zero adjustment

(a)Press PARA key until the PROG/SEG display shows (01-02).

(b)Adjust your calibration device to an output signal equal to the 0% range value (See Table 11-9), the signal need to be on the input for 10 to 15 seconds.

(c)Press ENT key after display stabilizes.

(2)PV span adjustment

(a)Press PARA key until the PROG/SEG display shows (01-03).

(b)Adjust your calibration device to an output signal equal to the 100% range value (See Table 11-9 and table 11-10).

(c)Press ENT key after display stabilizes.

Table 11-9.

Gain No.

PV Input 0%

PV Input 100%

Connecting Position

 

 

 

 

0

–12.785mV

110.000mV

Between 34(+) and 33(–)

 

 

 

 

1

–8.565mV

58.303mV

Between 34(+) and 33(–)

 

 

 

 

2

–13.788mV

40.481mV

Between 34(+) and 33(–)

 

 

 

 

3

–12.000mV

23.300mV

Between 34(+) and 33(–)

 

 

 

 

4

–1.000mV

11.000mV

Between 34(+) and 33(–)

 

 

 

 

5

–0.100V

1.100V

Between 34(+) and 33(–)

 

 

 

 

6

–0.500V

5.500V

Between 34(+) and 33(–)

 

 

 

 

7

–1.000V

11.000V

Between 34(+) and 33(–)

 

 

 

 

8

0.000mA

22.000mA

Between 34(+) and 33(–)

 

 

 

 

9

10.000

480.000

Between 34 and 33

 

 

 

 

10

10.000

178.000

Between 34 and 33

 

 

 

 

11

0.000

110.000

Between 34 and 33

 

 

 

 

12

0.000

45.000

Between 34 and 33

 

 

 

 

Table 11-10.

Gain No.

PV Input 0%

PV Input 100%

Connecting Position

 

 

 

 

16

–8.000mV

20.000mV

Between 28(+) and 29(–)

 

 

 

 

17

–20.000mV

70.500mV

Between 28(+) and 29(–)

 

 

 

 

18

–1.000V

11.000V

Between 27(+) and 26(–)

 

 

 

 

19

10.000

380.000

Between 30 and 29

 

 

 

 

20

0.000

110.000

Between 30 and 29

 

 

 

 

11-10

Page 174
Image 174
Sonic Alert DCP301 user manual PV calibration, Key, 11-10