Chapter 9. TROUBLESHOOTING

Auto-tuning (AT) is not canceled by pressing AT in the basic display state

Cause

Remedy

 

 

Key lock is enabled.

Set variable parameter L O C setting to 0 to 2.

 

 

Setting group other than “P A R A” is not displayed by pressing PARA by selecting the setting group in parameter set state

Cause

Remedy

 

 

Key lock is enabled.

Set variable parameter L O C setting to 0, 1 or 3.

 

 

Setting group other than “S E T” is not displayed by pressing PARA by selecting the setting group in parameter set state

Cause

Remedy

 

 

Key lock is enabled.

Set variable parameter L O C setting to 0 or 3.

 

 

The controller does not enter the setting entry state by pressing ENT in the param- eter setup state

Cause

Remedy

 

 

“– – – –” is displayed on the lower display.

This cannot be displayed nor set. This item sometimes

 

can be displayed or set by changing the setting of

 

related items.

 

 

Unchangeable data is displayed on the lower

This is a display-only item.

display.

 

 

 

The controller does not change to setup group selection state and setting entry state continues by pressing PARA in parameter setting entry state

Cause

Remedy

 

 

The controller displays items by PARA assign-

Press DISP to return the controller to the basic display

ment.

state, and press FUNC + PARA .

 

 

The controller does not change to program setup state by pressing FUNC + PROG in the basic display state

Cause

Remedy

 

 

The controller is in the constant-value opera-

Set constant-value operation data M .O D E setting to 0.

tion mode.

 

 

 

Key lock is enabled.

Set variable parameter L O C setting to 0, 1 or 3.

 

 

The controller does not change to the setting entry state by pressing ENT in the basic display state

Cause

Remedy

 

 

The program setup cannot be changed.

Set program parameter P R T C setting to 0.

 

 