Chapter 7. PARAMETER SETUP

Description of table data settings

t -A . 1 to t -A . b

t -b . 1 to t -b . b

These settings are for the A-axis (input) and B-axis (output) settings of input 1 linear- ization table approximation.

Both ends of the linearization table are fixed at -2000U, -2000U and 10000U,10000U. The linearization table is formed by connecting 11 points of table data settings be- tween the two ends.

Table data is set not by percentages but directly by engineering unit. When the range type is set to linear, set scaled values.

B-axis (output)

Fixed value

(10000, 10000)

 

 

10

11

 

 

8

9

 

7

 

 

6

 

 

5

 

 

4

 

A-axis (input)

 

 

3

 

 

2

 

 

1

 

 

Fixed value

 

 

(-2000, -2000)

 

 

Points on the broken-line, An and Bn, must be set so that they increase in the following way (A1, B1) = (0, 0), (A2, B2) = (100, 100) and so forth. If set points break this relation- ship, the point in conflict must be excluded to create the linearization table.

B-axis

B-axis

 

Excluded

(A3, B3)

 

(A3, B3)

 

(A2, B2)

(A2, B2)

(A1, B1)

A-axis

(A1, B1)

A-axis

When two equal points such as A1 and A2 are set for the A-axis, B1 shall be taken as the output value.

B-axis

(A2, B2)

(A1, B1)

A-axis

7-41