Chapter 8. PROGRAM SETUP

Setting up time events 1 to 5

(1)In the setting display state, move to the event 1 to 5 items of the segment to be set up on the programming map.

(2)If you press ENT , the upper display starts blinking to indicate start of entry to the No.1 setup.

(3)Press , , or to set to the No.1 setup ON time setting.

Setting range: 0:00 to 99:59 (h:min/min:s) 0.0 to 599.9 (0.1s)

(Select either of h:min or min:s as the time unit in setup data C 6 4. “:” is substituted by “.” as it cannot be displayed.)

(4)When you press ENT , blinking on the upper display stops. The lower display then starts blinking to indicate start of entry to the No.2 setup.

(When FUNC + CLR are pressed, the upper and lower displays both return to “- - - -” and blinking stops.)

(5)Press , , or to set to the No.2 setup ON time setting.

Setting range: ON time setting + 0:01 to 99:59 (h:min/min:s)

ON time setting + 0.1 to 599.9 (0.1s)

(6)When you press ENT , blinking on the upper display stops.

(When FUNC + CLR are pressed, the upper display returns to “- - - -” and stops blinking.)

Display

Program No. Segment No.

Pattern

tendency

ON time setting value

OFF time setting value

LEDs corresponding to EV1 to EV3 lit. T1 to T5 all out

“- - - -” is displayed for the setting values in non-set segments.

On models that do not support time events, event 1 to 5 items on the programming map are all skipped and not displayed. The table below shows time events by a «.

T T

Time event No.

T1

T2

T3

T4

T5

 

setting value

 

 

 

 

 

 

 

 

 

 

 

 

 

0

«

«

«

«

«

 

1

 

«

«

«

«

 

2

 

 

«

«

«

 

3

 

 

 

«

«

 

4

 

 

 

 

«

 

5

 

 

 

 

 

When setup data C 6 Q is set to 1, event 1 to 5 items on the programming map are all skipped and not displayed.

When the ON time is set to 99:59, “- - - -” is displayed as the OFF time, and the display does not blink.

When the ON time is set higher than the time setting of the pattern item, event output at that segment is OFF. However, note that event output is ON when the mode changes to the END mode at segments whose ON time and pattern item time are equal.

8-8

Page 135
Image 135
Sonic Alert DCP301 user manual Setting up time events 1 to, Time event No Setting value