Connecting Vanguard 7300 DC Power

Connecting DC Power to a Vanguard 7330 Version 1

Introduction

The DC-powered Vanguard 7330 has a pair of independent terminal blocks on each

 

power supply, shown in Figure 3-18and Figure 3-21.The detailed diagram,

 

Figure 3-21,shows the upper block, labeled A; the lower block is labeled B.

Note

To ensure continuous power to the unit, it is recommended that you connect both terminal blocks of each power supply, each to a separate power source.

ESD Bond

Point

Serial No. Location

DC Power Connectors

(Detailed in next figure)

 

Figure 3-18. Vanguard 7330 Version 1 DC Power Connectors

Vanguard 7300 DC

Power Terminal

Block

Figure 3-19. Vanguard 7330 Version 1 DC Power Terminal Block Details

3-24

Vanguard 7300 Installation