7-60

ADMINISTRATION OPTIONS AND REQUIREMENTS — GENERIC 2

 

 

 

 

 

Criteria for Switching Back to the Primary

 

At the end of the 1-hour interval, the slip count is analyzed. If the primary slip

 

count is less than 2, then a switch back to the primary is made. Also, if the primary

 

has a slip count of 44 or less and if the secondary and 50% of those DS1s that are

 

enabled for slip enable have reached their maximum slip count of 88, then a switch

 

back to the primary is made.

Field 11

Offers the options external loop not available (0) or external loop available (1).

 

The external loop available option should only be selected when demand diagnostic

 

maintenance is done and then only after the interface has been busied out. This

 

option is used with procedure 620, Test 2 to extend the range of the test to include

 

the network channel-terminating equipment (NCTE) and the connecting facility

 

(any external equipment to the point of the DS1 loop around). The test requires

 

that either the colocated or the distant NCTE be physically optioned for loopback

 

mode.

 

The external loop available option should only be used for the duration of the test.

Field 12

Specifies whether (1) or not (0) the associated T1-span is used as an incoming

 

synchronization source to the switch. The network synchronization diagram should

 

show those transmission facilities that are used for synchronization. Each switch

 

permits a maximum of two interfaces (one primary and one secondary) to be

 

translated (1) in field 12. However, there is no requirement to have both.

 

For the case where Generic 2 is the master timing server, neither primary or

 

secondary is administered.

 

Each Generic 2 that is equipped with a DS1 will also contain a TN463

 

synchronization clock (SC). For single-module systems, the SC is located in the

 

module control carrier along with the TN460 module clock. For multimodule

 

systems, the SC is located in the TMS carrier. The SC should have previously been

 

assigned in procedure 250.