Master Programming Level
SERVICE TERMINAL 1=RING COUNT
Service Terminal Screen #2
ON BOARD DACT
1=SERVICE TERMINAL 2=CENTRAL STATION 3=MANUAL DIAL MODE
On Board DACT Screen #2
Programming
3.6.9.2.4.3 Ring CountThe ring count designates the number of rings allowed on the phone line prior to answering an incoming call from a service terminal. The factory default is 3 which means the control panel will not answer an incoming call until 3 rings are detected. This entry may be programmed for 1 to 25 rings. A setting of 00 prevents the panel from answering incoming calls.
To change the Ring Count, press 1 while viewing the Service Terminal Screen #2. The following screen will be displayed:
RING COUNTA flashing cursor will appear in the lower left corner of the display. Enter the two- digit ring count which can be a value between 00 and 25. After the second digit is entered, the display will return to the Service Terminal screen.
3.6.9.2.5 Central StationCentral Station programming configures the control panel DACT for contacting the central station. Pressing 2 while viewing On Board DACT Screen #2 will cause the following screens to be displayed:
CENTRAL STATION 1=REPORTING DISABLED2=REPORT BACKUP 3=CALL LIMITCentral Station Screen #1CENTRAL STATION 1=PRIMARY
2=SECONDARY 3=REPORT STYLECentral Station Screen #2
3.6.9.2.5.1 Reporting EnableTo enable the DACT for reporting FACP activity to the central station, press 1 while viewing Central Station Screen #1 so the display reads Reporting Enabled. Each press of the 1 key will toggle the display between Reporting Disabled and Reporting Enabled.
101 |