Installation

Optional Module Installation

2.9.1 4XTMF Transmitter Module Installation

The 4XTMF provides a supervised output for a local energy municipal box transmitter in addition to alarm and trouble reverse polarity. A jumper option allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. A disable switch allows disabling of the transmitter output during testing to prevent accidental calling of the monitoring service.

Local Energy Municipal Box Service (NFPA 72 Auxiliary Fire Alarm Systems): Supervisory Current: 5.0 mA

Trip Current: 350 mA (subtracted from notification appliance power)

Coil Voltage: 3.65 VDC

Maximum Coil Resistance: 14.6 ohms

Maximum allowable wire resistance between panel and trip coil: 3 ohms Municipal Box wiring can leave the building

Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended for connection to a polarity reversal circuit or a Remote Station receiving unit having compatible ratings:

Maximum load for each circuit: 10 mA

Reverse polarity output voltage: 24 VDC

Remote Alarm and Remote Trouble wiring can leave the building

Before installing the module, place the disconnect switch to the right (disconnect) position to prevent accidental activation of the municipal box. Note that a Disconnect LED will illuminate after the module is installed in the MS-9200UDLS. In addition, the System Trouble LED will turn on to indicate the Disconnect condition.

 

 

 

Note: 4XTMF Module is not suitable for

 

 

 

 

transmitting reverse polarity supervisory signal.

 

 

 

 

 

 

 

 

 

 

 

 

 

}Remote Alarm (power-limited)*

* Wiring from these

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

terminals can exit the

 

 

 

 

 

 

 

 

 

 

 

 

}Remote Trouble (power-limited)*

 

 

 

 

 

 

 

 

 

 

 

 

protected premises.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No connection

Dummy load terminals

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6 and 7 (4.7kΩ, ¼ watt

 

 

 

 

 

 

 

 

 

 

 

 

 

}Municipal Box (nonpower-limited)*

 

 

 

 

 

 

 

 

 

 

 

 

 

resistor) if Municipal

 

 

 

 

 

 

 

 

 

 

 

 

 

+

-

 

 

 

 

 

 

 

-

 

 

 

 

 

Box is not connected.

+

-

+

 

 

 

 

 

 

1

2

3

4

5 6

7

 

Polarities are shown for module activation

Disconnect LED

4xtmfl.cdr

Disconnect Switch shown in disconnect position

TBL Jumper

Connect to FACP J10 & J11

Figure 2.15 4XTMF Transmitter Module

38