NFPA Standard-Specific RequirementsCorrelations

APPENDIX C

NFPA Standard-Specific Requirements

 

The MS-9200UDLShas been designed for use in commercial, industrial and institutional

 

applications and meets the requirements for service under the National Fire Protection

 

Association (NFPA) Standards outlined in this Appendix. The minimum system

 

components required for compliance with the appropriate NFPA standard are listed

 

below:

MS-9200UDLS Control Panel

Contains the main control board, cabinet (backbox and door), main power supply transformer and power supply.

Batteries

Refer to "Power Supply Calculations" on page 163, for Standby Power Requirements.

Initiating Devices

Connected to one of the control panel's Initiating Device Circuits.

Notification Appliances

Connected to the control panel's Notification Appliance Circuits via a control module.

The following additional equipment is needed for compliance with the NFPA 72 standards listed below:

NFPA 72 NATIONAL FIRE ALARM STANDARDS FOR:NFPA 72 Central Station Service (Protected Premises Unit) or Remote StationService

Onboard Digital Alarm Communicator Transmitter for connection to a compatible listed Central Station DACR or Protected Premises Receiving Unit. This unit must be installed as outlined in "Digital Alarm Communicator/Transmitter" on page 17.

OR

4XTMF Transmitter Module for connection to the RS82 Remote Station Receiver. See Figure C.2, “Remote Station Connection Using 4XTMF Module,” on page 176, for installation instructions for this unit.

NFPA 72 Auxiliary Fire Alarm System

F Transmitter Module for connection to a compatible listed Local Energy Municipal

Box. This unit must be installed as illustrated in the section titled "4XTMF

Transmitter Module Installation" on page 38 and as outlined in Figure C.1, “Municipal

Box Connected to F Transmitter Module,” on page 175.

NFPA 72 Proprietary Fire Alarm System

MS-9200UDLS Alarm, Trouble and Supervisory contacts connected to Transmitter(s). See Figure C.3, “Proprietary Protective Signaling System,” on page 177, for installation instructions for this unit.

174

MS-9200UDLS PN 52750:A 11/04/05