User Programming | Programming |
3.2 User Programming
The
!control panel are enabled.
•Autoprogramming Feature - This is a convenient method for quickly bringing the FACP addressable SLC devices
•Manual programming or editing, using the FACP keypad or a PC keyboard
•
The System All Normal screen will be displayed in a programmed system with no active alarms, troubles or supervisories, as illustrated below:
| HONEYWELL LIFE SAFETY |
| |
| SYSTEM ALL NORMAL |
| |
| 10:00A | 012102 |
|
|
|
| |
Programming, Read Status and Manual Dial mode can be entered while the panel is in | |||
any mode of operation. If the panel is in alarm, the alarm condition must be | |||
acknowledged before entering any other mode. To access any of the programming or | |||
read status features, the Enter or Mode key must be pressed, which will cause the LCD | |||
to display the following: |
|
| |
|
| ||
| 1=READ STATUS MODE |
| |
| 2=PROGRAMMING MODE |
| |
| 3=MANUAL DIAL MODE |
| |
|
|
| |
Pressing 1, while this screen is being displayed, will cause the control panel to enter the | |||
Read Status Mode which allows the user to view the programmed features and status of | |||
the control panel The Read Status feature is not password protected. Refer to "Read | |||
See Page Status" on page 140 for a detailed description of this feature. |
Pressing 2 will select user Programming Mode which may only be accomplished by an authorized person. After pressing 2, a screen will prompt for a password. After entering the correct password, the user may select from a list of programming options.
Pressing 3 will select the Manual Dial Mode which allows the user to enter a troubleshoot mode of operation.
Exit Programming, Read Status and Manual Dial ModeThe programmer can exit any mode by repeatedly pressing the keypad ESC (Escape) key until the display reads System All Normal. Note that the data which is entered during Programming mode is not saved until the programmer exits this mode by repeatedly pressing the ‘ESC’ key. If the Reset key is pressed or power is lost before exiting Programming mode, all data just entered will be lost.
43 |