Power Supply Calculations | Calculating the System Current Draw |
7.3 Calculating the System Current Draw
7.3.1 OverviewThe control panel must be able to power all internal and external devices continuously during the
When calculating current draw and the battery size, note the following:
•‘Primary’ refers to the main power source for the control panel
•‘Secondary’ refers to the control panel’s backup batteries
•All currents are given in amperes (A). Table 7.2 shows how to convert milliam- peres and microamperes to full amperes.
Table 7.2 Converting to Full AmperesTo convert... | Multiply | Example | |
|
|
| |
Milliamperes (mA) to | mA x 0.001 | 3 mA x 0.001 = 0.003A | |
amperes (A) | |||
|
| ||
|
|
| |
Microamperes (µA) to | µA x 0.000001 | 300 µA x 0.000001 = 0.0003 A | |
amperes (A) | |||
|
| ||
|
|
|
7.3.2How to Use Table 7.3 on page 165 to Calculate System Current Draw
Use Table 7.3 on page 165 to calculate current draws as follows:
1.Enter the quantity of devices in all three columns
2.Enter the current draw where required. Refer to the Device Compatibility Document for compatible devices and their current draw
3.Calculate the current draws for each in all columns
4.Sum the total current for each column
5.Copy the totals from Column 2 and Column 3 to Table 7.4 on page 166 Following are the types of current that can be entered into Table 7.3 on page 165:
Calculation Column 1 - The primary supply current load that the control panel must support during a
Calculation Column 2 - The primary supply current load that the control panel must support during a fire alarm condition, with AC power applied.
Calculation Column 3 - The standby current drawn from the batteries in a
164 |