NFPA Standard-Specific Requirements

Correlations

NFPA 72 Remote Station Protective Signaling System

Notes:

1.Cut Jumper JP3 on the MS-9200UDLS main circuit board to supervise placement of the 4XTMF module.

2.Refer to "4XTMF Transmitter Module Installation" on page 38 for detailed information.

RS82 Remote Station Receiver UL listed.

Refer to Instruction Manual for Remote Station Receiver

Model RS82.

Cutting TBL Jumper allows the reverse polarity circuit to open

with a system trouble condition if no alarm condition exists.

 

Polarity Shown is

+

- Normal Standby

+

Power-limited

-

(Dummy load with a 4.7KΩ, ¼ watt resistor when no connection is made)

4XTMF Transmitter Module

Figure C.2 Remote Station Connection Using 4XTMF Module

176

MS-9200UDLS PN 52750:A 11/04/05