Correlations

NFPA Standard-Specific Requirements

NFPA 72 Auxiliary Fire Alarm System

All connections are power-limited and supervised. This application is not suitable for separate transmission of sprinkler supervisory or trouble conditions.

Notes:

1.3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box.

2.Cut JP3 on the MS-9200UDLS main circuit board to supervise placement of 4XTMF module and circuit.

3.Cut JP2 on the MS-9200UDLS main circuit board to enable FACP Supervisory relay.

4.Refer to "4XTMF Transmitter Module Installation" on page 38 for detailed information.

Figure C.1 Municipal Box Connected to F Transmitter Module

Polarities shown in alarm condition

FIRE

+

Municipal Box

Circuit -

Gamewell Model M34-56

Local Energy Municipal Box

Nonpower-limited

+-

F

Figure C.1 Municipal Box Connected to 4XTMF Transmitter Module

MS-9200UDLS PN 52750:A 11/04/05

175