Programming and Passwords | Programming |
To access user Programming mode, press the Enter or Mode key. The LCD will display the following:
1=READ STATUS MODE 2=PROGRAMMING MODE 3=MANUAL DIAL MODETo enter the user Programming mode, press 2. The display will read as follows:
PROGRAMMINGENTER PASSWORD*****
Entering the Master level password (default 00000) will cause the following screen to appear:
PROGRAMMING 1=AUTOPROGRAM 2=POINT PROGRAM 3=ZONE SETUP
If the Maintenance level password (default 11111) is entered, the following screen will appear:
PROGRAMMING 1=POINT PROGRAM 2=HISTORY
3=PROGRAM CHECK
Note that in the two preceding screens, an arrow appears to inform the programmer that additional options can be viewed by pressing the keypad down arrow key.
45 |