Programming
PROGRAMMING 1=AUTOPROGRAM 2=POINT PROGRAM 3=ZONE SETUP
Programming Screen #1
Master Programming Level
3.6.2 Point Program
The Point Program option allows the programmer to add a new addressable device to an SLC loop, delete an existing device from a loop or change the programming for an existing device. Pressing 2, while viewing Programming Screen #1, will select the Point Program option and display the following screen:
POINT PROGRAM
SELECT TYPE 1=DETECTOR 2=MODULE
Point Program Screen
3.6.2.1 Detector Programming
Pressing 1, while viewing the Point Program Screen, will allow the programmer to add, delete or change the programming of an addressable detector. The following screen will be displayed by the control panel:
DETECTOR
1=ADD
2=DELETE
3=EDIT
Detector Screen
3.6.2.1.1 Add Detector
Pressing 1 while viewing the Detector Screen will display the following screen which allows the programmer to add a new detector address to programming:
ADD DETECTOR
ENTER DETECTOR#
***
Add Detector Screen
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit detector address, such as 005.
When the last digit is
DETECTOR TYPE 1=SMOKE(PHOTO) 2=USER-DEFINED-1 3=SMOKE(ION)
Press the down arrow key to view additional choices. Press the number corresponding to the desired selection to program that type to the newly added detector.
48 |