Product Description | Specifications |
Battery (Lead Acid Only) - J9
Maximum Charging Circuit: Normal Flat Charge - 27.6 VDC @ 0.80 amp
Maximum Battery Charger Capacity: 18 Amp Hour
Note: Jumper JP5, on the FACP main circuit board, must be removed to disable the FACP battery charger when using an external battery charger.
Communication Loop - TB10
24 VDC nominal, 27.6 VDC maximum
Maximum length is 10,000 ft. (3,000 m) total twisted, shielded pair length or 3,000 ft. (900 m) untwisted, unshielded pair length
Maximum loop current is 400 mA (short circuit) or 100 mA (normal) Maximum loop resistance is 40 ohms
Supervised and
Notification Appliance Circuits - TB3 & TB4
Each Terminal Block provides connections for two Style Y (Class B) or one Style Z (Class A) for a total of Four Style Y (Class B) or two Style Z (Class A) NACs Style is configured using NACKEY card plugged into JP6 on main board Special Application
Maximum voltage drop in wiring: 2.0 VDC
Nominal operating voltage: 24 VDC
Maximum signaling current per circuit: 2.5 amps (see Figure 1.1 on page 15)
Two Programmable Relays and One Fixed Trouble Relay - TB5, TB6 & TB7
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Refer to Figure 2.6 on page 32 for information on
Nonresettable Special Application Power (24 VDC Nominal) - TB1, Terminals 1 (+) & 2
Jumper selectable (JP4) for conversion to resettable power output Maximum ripple voltage: 10mVRMS
Total DC current available from each output is up to 0.5 amps (see Figure 1.1)
Maximum ripple voltage: 10 mVRMS
Up to 0.5 amps is available for powering
Refer to the Device Compatibility Document for listed compatible devices
Remote Sync Output - TB2
Remote power supply synchronization output 24 VDC nominal special application power Maximum current is 40 mA
Supervised and
14 |