Central Station Communications

 

 

Read Status

 

 

The control panel is capable of reporting detailed messages depending upon the format

 

 

in use. Table 5.1

shows the reporting structure for all formats.

 

 

 

Table 5.1 Format Selection

 

 

 

 

 

 

 

 

 

 

Format

Format

Format

Format

 

 

 

 

 

 

 

Report

3+1/4+1/Standard

3+1/4+1/Expanded

4+2/Standard

4+2/Expanded

 

 

4+1 Express

 

4+2 Express

 

 

 

 

 

 

 

 

Alarm

SSS(S) A

SSS(S) A

SSSS AA2

SSSS AZ

 

 

 

AAA(A) Z

 

 

 

 

 

 

 

 

 

Alarm Restore

SSS(S) RA

SSS(S) RA

SSSS RARA2

SSSS RAZ

 

 

 

RARARA(RA) Z

 

 

 

 

 

 

 

 

 

Zone Trouble

SSS(S) TZ

SSS(S) TZ

SSSS TZTZ2

SSSS TZZ

 

(Zone Open)

 

TZTZTZ(TZ) Z

 

 

 

 

 

 

 

 

 

Zone Trouble Restore

SSS(S) RTZ

SSS(S) RTZ

SSSS RTZRTZ2

SSSS RTZZ

 

 

 

RTZRTZRTZ(RTZ) Z

 

 

 

 

 

 

 

 

 

System Trouble

SSS(S) TS

SSS(S) TS

SSSS TSTS2

SSSS TSY

 

 

 

TSTSTS(TS) Y

 

 

 

 

 

 

 

 

 

System Trouble Restore

SSS(S) RTS

SSS(S) RTS

SSSS RTSRTS2

SSSS RTSY

 

 

 

RTSRTSRTS(RTS) Y

 

 

 

 

 

 

 

 

 

Zone Disable

SSS(S) DZ

SSS(S) DZ

SSSS DZDZ2

SSSS DZZ

 

 

 

DZDZDZ(DZ) Z

 

 

 

 

 

 

 

 

 

Zone Disable Restore

SSS(S) RDZ

SSS(S) RDZ

SSSS RDZRDZ2

SSSS RDZZ

 

 

 

RDZRDZRDZ(RDZ) Z

 

 

 

 

 

 

 

 

 

Low Battery

SSS(S) L

SSS(S) L

SSSS LL2

SSSS LL2

 

 

 

LLL(L) L2

 

 

 

 

 

 

 

 

 

Low Battery Restore

SSS(S) RL

SSS(S) RL

SSSS RLRL2

SSSS RLRL2

 

 

 

RLRLRL(RL) RL2

 

 

 

 

 

 

 

 

 

AC Loss

SSS(S) P

SSS(S) P

SSSS PP2

SSSS PP2

 

 

 

PPP(P) P2

 

 

 

 

 

 

 

 

 

AC Loss Restore

SSS(S) RP

SSS(S) RP

SSSS RPRP2

SSSS RPRP2

 

 

 

RPRPRP(RP) RP2

 

 

 

 

 

 

 

 

 

Fire Drill

SSS(S) FD

SSS(S) FD

SSSS FDFD2

SSSS FDFD2

 

 

 

FDFDFD(FD) FD2

 

 

 

 

 

 

 

 

 

Fire Drill Restore

SSS(S) RFD

SSS(S) RFD

SSSS RFDRFD2

SSSS RFDRFD2

 

 

 

RFDRFDRFD(RFD) RFD2

 

 

 

 

 

 

 

 

 

Supervisory Condition

SSS(S) V

SSS(S) V

SSSS VV2

SSSS VZ

 

 

 

VVV(V) Z

 

 

 

 

 

 

 

 

 

Supervisory Condition

SSS(S) RV

SSS(S) RV

SSSS RVRV2

SSSS RVZ

 

Restore

 

RVRVRV(RV) Z

 

 

 

 

 

 

 

 

 

Test Report

SSS(S) X

SSS(S) X

SSSS XX2

SSSS XX2

 

 

 

 

 

 

 

Upload or Download

SSS(S) UD

SSS(S) UD

SSS UDUD2

SSS UDUD2

 

 

 

 

 

 

Refer to Table 5.2 for an explanation of each letter code in Table 5.1 . Refer to Table 5.3 for a list of compatible receivers.