Programming
SYSTEM SETUP 1=TIMERS 2=NAC 3=RELAYS
System Setup Screen #2
TIMERS
1=PAS DELAY 000 2=PRE SIGNAL 000 3=WATERFLOW 000
Timer Screen #1
Master Programming Level
Pressing 3 while viewing Daylight Savings Screen #1 will display two
Pressing 1 while viewing Daylight Savings Screen #2 will display another screen which allows the programmer to select the month that daylight savings time will end. In this
Pressing 2 while viewing Daylight Savings Screen #2 will display two
3.6.5.4 Timers
Timer delays for PAS,
| TIMERS |
|
|
| 1=PAS DELAY | 000 |
|
| 2=PRE SIGNAL | 000 |
|
| 3=WATERFLOW | 000 |
|
|
|
|
|
| Timer Screen #1 |
|
|
|
|
|
|
| TIMERS |
|
|
| 1=AC LOSS DELAY | 000 |
|
|
|
|
|
Timer Screen #2
3.6.5.4.1 PAS (Positive Alarm Sequence) Delay
The factory default setting for PAS is 000 for no delay. To select a PAS delay of 001 to 180 seconds for all devices programmed for PAS, press 1 while viewing Timer Screen #1. The following display will appear:
PAS DELAY
RANGE 0-180 SECONDS
PAS Delay Screen
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of three digits, such as 005 for five seconds. Upon entering the third digit, the time delay will be stored in the control panel memory and the display will return to the Delay Screen which will indicate the new delay time.
84 |