Programming |
| Master Programming Level | |
| 4+2 Standard, 4+2 Express, 3 + 1, 4 + 1 and 4+2 Expanded Formats | ||
| The information shown in Table 3.3 | is automatically programmed for the Central | |
| Station phone number Event Codes when any of these Formats are selected. Enter | ||
| 00 for an Event Code Setting to disable the report. | ||
| Table 3.3 Event Codes |
|
|
|
|
| |
Event Description | Event Code Settings |
| |
| Active | Restoral |
|
|
|
|
|
PULL STATION | 11 | E1 |
|
11 | E1 |
| |
WATERFLOW | 11 | E1 |
|
11 | E1 |
| |
SMOKE (PHOTO) | 11 | E1 |
|
11 | E1 |
| |
SMOKE (ION) | 11 | E1 |
|
11 | E1 |
| |
HEAT DETECT | 11 | E1 |
|
11 | E1 |
| |
SMOKE | 11 | E1 |
|
11 | E1 |
| |
DUCT SUPERVISORY | 81 | E1 |
|
81 | E1 |
| |
not used | 00 | 00 |
|
not used | 00 | 00 |
|
not used | 00 | 00 |
|
not used | 00 | 00 |
|
MONITOR | 11 | E1 |
|
11 | E1 |
| |
not used | 00 | 00 |
|
not used | 00 | 00 |
|
SMOKE CONVEN | 11 | E1 |
|
11 | E1 |
| |
HEAT DETECT | 11 | E1 |
|
11 | E1 |
| |
MEDIC ALERT | 00 | 00 |
|
00 | 00 |
| |
HAZARD ALERT | 00 | 00 |
|
00 | 00 |
| |
TORNADO ALRT | 00 | 00 |
|
00 | 00 |
| |
not used | 00 | 00 |
|
not used | 00 | 00 |
|
TAMPER | 81 | E1 |
|
81 | E1 |
| |
MON SUPERVISORY | 81 | E1 |
|
81 | E1 |
| |
MON SUPERV AUTO | 81 | E1 |
|
81 | E1 |
| |
POWER MON | 81 | E1 |
|
81 | E1 |
| |
TROUBLE MON | POINT_FAULT code will always be transmitted |
| |
POINT_FAULT code will always be transmitted |
| ||
PROCESS MON | 00 | 00 |
|
110 |