Programming

Master Programming Level

3+1, 4+1 Express and 4+1 Standard

The information shown in Table 3.2 is automatically programmed for the Central Station phone number Event Codes when any of these Formats are selected. Enter 0 for an Event Code Setting to disable the report.

Table 3.2 Event Codes

Event Description

Event Code Settings

 

Active

Restoral

 

 

 

PULL STATION

1

E

MON-USER-DEF-1

1

E

WATERFLOW

1

E

MON-USER-DEF-2

1

E

SMOKE (PHOTO)

1

E

DET-USER-DEF-1

1

E

SMOKE (ION)

1

E

DET-USER-DEF-2

1

E

HEAT DETECT

1

E

DET-USER-DEF-3

1

E

SMOKE DUCT-P

1

E

DET-USER-DEF-4

1

E

DUCT SUPERVISORY

8

E

DET-USER-DEF-5

8

E

not used

0

0

not used

0

0

not used

0

0

not used

0

0

MONITOR

1

E

MON-USER-DEF-3

1

E

not used

0

0

not used

0

0

SMOKE CONVEN

1

E

MON-USER-DEF-5

1

E

HEAT DETECT

1

E

MON-USER-DEF-6

1

E

MEDIC ALERT

0

0

MON-USER-DEF-7

0

0

HAZARD ALERT

0

0

MON-USER-DEF-8

0

0

TORNADO ALRT

0

0

MON-USER-DEF-9

0

0

not used

0

0

not used

0

0

TAMPER

8

E

MON-USER-DEF-11

8

E

MON SUPERVISORY

8

E

MON-USER-DEF-12

8

E

MON SUPERV AUTO

8

E

MON-USER-DEF-13

8

E

POWER MON

6

A

MON-USER-DEF-14

6

A

TROUBLE MON

POINT_FAULT code will always be transmitted

MON-USER-DEF-15

POINT_FAULT code will always be transmitted

PROCESS MON

0

0

108

MS-9200UDLS PN 52750:A 11/04/05