Programming | Master Programming Level |
The information shown in Table 3.2 is automatically programmed for the Central Station phone number Event Codes when any of these Formats are selected. Enter 0 for an Event Code Setting to disable the report.
Table 3.2 Event CodesEvent Description | Event Code Settings | |
| Active | Restoral |
|
|
|
PULL STATION | 1 | E |
1 | E | |
WATERFLOW | 1 | E |
1 | E | |
SMOKE (PHOTO) | 1 | E |
1 | E | |
SMOKE (ION) | 1 | E |
1 | E | |
HEAT DETECT | 1 | E |
1 | E | |
SMOKE | 1 | E |
1 | E | |
DUCT SUPERVISORY | 8 | E |
8 | E | |
not used | 0 | 0 |
not used | 0 | 0 |
not used | 0 | 0 |
not used | 0 | 0 |
MONITOR | 1 | E |
1 | E | |
not used | 0 | 0 |
not used | 0 | 0 |
SMOKE CONVEN | 1 | E |
1 | E | |
HEAT DETECT | 1 | E |
1 | E | |
MEDIC ALERT | 0 | 0 |
0 | 0 | |
HAZARD ALERT | 0 | 0 |
0 | 0 | |
TORNADO ALRT | 0 | 0 |
0 | 0 | |
not used | 0 | 0 |
not used | 0 | 0 |
TAMPER | 8 | E |
8 | E | |
MON SUPERVISORY | 8 | E |
8 | E | |
MON SUPERV AUTO | 8 | E |
8 | E | |
POWER MON | 6 | A |
6 | A | |
TROUBLE MON | POINT_FAULT code will always be transmitted | |
POINT_FAULT code will always be transmitted | ||
PROCESS MON | 0 | 0 |
108 |