Programming

POINT PROGRAM SELECT TYPE 1=DETECTOR 2=MODULE

Point Program Screen #2

Master Programming Level

As an example, the user could quickly enter ‘FLR_3_ROOM_305’ as follows:

1.The cursor is on the first letter of the Adjective field. Press the zero key twice to display FLR_3

2.With the cursor on the first letter of the Noun field, press the zero key twice to recall the display ROOM_304. The cursor automatically jumps from the first to the last letter of the Noun field

3.With the cursor on the last letter of the Noun field, press the zero key again to increment the room number to 305

4.Press the right arrow key to advance the zone field

5.Select a zone number from 00 to 99. Z00 (default zone) is the general alarm zone. Z01 through Z99 may be selected to link software zones

3.6.2.2Module Programming

Pressing 2, while viewing Point Program Screen #2, will allow the programmer to add, delete or change the programming of an addressable module. The following screen will be displayed by the control panel:

MODULES

1=ADD

2=DELETE

3=EDIT

Modules Screen

3.6.2.2.1 Add Module

Pressing 1 while viewing the Modules Screen will display the following screen which allows the programmer to add a new module address to programming:

ADD MODULE

ENTER MODULE#

***

Add Module Screen #1

A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit module address, such as 005.

When the last digit is keyed-in, the following screen will be displayed:

ADD MODULE 1=CONTROL 2=MONITOR

Add Module Screen #2