Master Programming Level | Programming |
3.6.5.4.2 |
The factory default setting for
2 while viewing Timer Screen #1. The following screen will be displayed:
PRESIGNAL DELAYRANGE
TIMER
1=PAS DELAY 000 2=PRE SIGNAL 000 3=WATERFLOW 000
Timer Screen #1
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of three digits, such as 009 for nine seconds. Upon entering the third digit, the time delay will be stored in the control panel memory and the display will return to the Delay Screen which will indicate the new delay time.
Note that the FACP can be programmed for either PAS or
A delay can be added prior to declaring a waterflow type of alarm. Be careful to include any
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of two digits, such as 25 for
85 |