Central Station Communications

Transmittal Priorities

5.1 Transmittal Priorities

The integral communicator transmits highest priority events first. Events, in terms of priority, are listed below in descending order:

1.Alarms (highest priority level) Pull stations

Waterflow Smoke detector Other alarm types

2.Supervisory Zone

3.System Troubles

Zone disabled

Fire drill

AC fail (after delay)

Zonal faults

Earth fault

Low battery

Telephone line fault

Notification Appliance Circuits fault

Communication trouble

Annunciator trouble

System off normal

4.Restoral Reports

Zone alarm Supervisory Zone(s) enabled Fire drill

AC

Zone fault Earth Battery Telephone line

Notification Appliance Circuits Communication Annunciator trouble

System off normal

5.24 Hour Test (lowest priority)

Red LEDs are provided on the circuit board to identify which telephone line is activated. Also, a green LED labeled Kissoff will turn on whenever the control panel has successfully transmitted reports to the Central Station. The Kissoff LED may turn on several times during communications with a Central Station.

The table below shows UL listed receivers which are compatible with the MS-