Master Programming Level

NAC #

1=AUTO SILENCE 2=CODING

TEMPORAL

NAC Screen #2

Programming

3.6.5.5.4 Auto Silence

The Auto Silence feature, when enabled, automatically silences all main circuit board silenceable notification appliances after a programmed length of time. To enable this feature and program the time delay before Auto Silence activation, press

1 while viewing NAC Screen #2. The following screens will be displayed:

AUTO SILENCE 1=NO2=5 MINUTES 3=10 MINUTESAuto Silence Screen #1AUTO SILENCE 1=15 MINUTES 2=20 MINUTES 3=25 MINUTESAuto Silence Screen #2AUTO SILENCE 1=30 MINUTESAuto Silence Screen #3

To disable the Auto Silence feature, press 1 for No while viewing Auto Silence Screen #1. To enable the Auto Silence feature, press the number corresponding to the time delay which will elapse before Auto Silence activates. This information will be stored in memory and the display will return to NAC Screen #2.

Note: All silenceable control modules as well as the remote power supply sync will be controlled by the Autosilence timer for NAC 1.

3.6.5.5.5Coding (only for NACs not programmed as Sync Strobe Type)

The Coding feature allows the programmer to select the type of output that the main circuit board notification appliances will generate when activated. Pressing 2 while viewing NAC Screen #2 will cause the following displays to appear:

CODING1=STEADY2=MARCH TIME 3=CALIFORNIACoding Screen #1CODING 1=TEMPORAL 2=TWO STAGE 3 MIN 3=TWO STAGE 5 MINCoding Screen #2