Optional Module Installation

Installation

2.9.3Digital Communicator and Annunciators

2.9.3.1ACM-8RF Relay Control Module

Reference

Manual

The ACM-8RF module provides eight Form-C relays with contacts rated for 5 amps. When installed with an MS-9200UDLS FACP, the ACM-8RF modules provide relay activation for each of the 99 possible FACP zones plus special functions. Options exist to allow for alarm only or alarm and trouble activation per zone. Output activation for general alarm, general trouble, general supervisory, NAC fault, AC fail, walktest start and battery trouble are also available. The ACM- 8RF can be mounted remotely in an ABS-8RF annunciator surface-mount backbox. Refer to the ACM-8RF manual for information on setting module switches for addressing and relay functions.

2.9.3.2 ACS and AFM Series Annunciators

ACS and AFM Series Annunciators provide visual indications of FACP status in remote locations. Refer to the appropriate annunciator manual for information on installation, wiring and operation.

Annunciator addressing is specific to the MS-9200UDLS control panel. The following table describes the annunciator addresses and the corresponding addressable devices that will be annunciated at each annunciator address.

ACM Annunciator Address

Annunciator Displays the Following Points

1

8 General System Status Points & Zones 1 - 56

2

Zones 57 - 99 & 4 NACs

3

SLC Loop, Module Addresses 1 - 64

4

not used

5

SLC Loop, Module Addresses 65 - 99

6

not used

7

not used

8

SLC Loop, Detector Addresses 1 - 64

9

not used

10

SLC Loop, Detector Addresses 65 - 99

11

not used

12

not used

13

not used

14

not used

15

not used

16

not used

17

not used

18

not used

19

not used

20

8 General System Status Points & Zones 1 - 56

21

Zones 57 - 99 & 4 NACs

22

SLC Loop, Module Addresses 1 - 64

23

not used

24

SLC Loop, Module Addresses 65 - 99

25

not used

26

not used

27

SLC Loop, Detector Addresses 1 - 64

28

not used

29

SLC Loop, Detector Addresses 65 - 99

30

not used

31

not used

32

not used

The MS-9200UDLS must be programmed for the annunciators installed on the system. Refer to "Annunciators/UDACT" on page 96 for information on annunciator programming. Make certain to program the annunciator addresses that have been physically installed on the system.

Note: The 8 General System Status Points include the following:

• General Alarm

• Alarm Silenced

• Battery Fault

• General Trouble

• System Off Normal

• NAC Fault

• General Supervisory

• AC Loss

 

MS-9200UDLS PN 52750:A 11/04/05

41