Programming

SECTION 3

Programming Data Entry

Programming

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION

AND OTHER INVOLVED PARTIES

This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as indicated below:

Program feature

Permitted in

Possible settings

Settings permitted

or option

UL 864? (Y/N)

in UL 864

 

 

 

Refer to "Trouble Call Limit (Dialer Runaway Preven-

 

 

 

tion)" on page 102.

Trouble Call Limit

 

 

Trouble Call Limit = 0 (factory default): unlimited

Trouble Call Limit

N

= 0 for unlimited

calling to Central Station for any trouble condition

Central Station

 

 

 

 

Trouble Call Limit = 1 - 99: limits call for each unique

trouble calls

 

 

 

 

 

trouble to from 1 to 99 within a 24 hour period

 

 

 

 

 

3.1 Programming Data Entry

Programming can be accomplished using the MS-9200UDLS keypad or by connecting an optional standard computer keyboard. The keyboard can be connected to the PS-2 connector J3 on the control panel main circuit board.

The information presented in this section refers to programming the MS-9200UDLS via the onboard keypad. If an optional computer keyboard is connected to the MS- 9200UDLS main circuit board, the following table describes the keyboard keys which correspond to the onboard keypad keys.

Keypad Keys

Computer Keyboard Keys

 

 

1st Event

Home

 

 

CLR

Delete

 

 

ESC

Esc

 

 

RECALL

Insert

 

 

*

*

 

 

#

#

 

 

A - Z

A - Z

 

 

0 - 9

0 - 9

 

 

(on QZ key)

Space bar

 

 

 

 

/

/

 

 

 

 

 

 

 

 

 

 

 

 

ENTER

Enter

 

 

ACK/STEP

F1

 

 

SILENCE

F2

 

 

DRILL

F3

 

 

RESET

F4

 

 

42